Error 10: Communication error between BACnet Integration Gateway Systems
The system loses communication with the Airzone BACnet Interface. Check that the gateway is properly connected to the
automation bus of the Main Board.
Error 11: Gateway-AC Unit communication error
The system loses communication with the AC unit. The system will open all the zones and deactivate the control from the
thermostats, only allowing the operation of the unit from the thermostat of its manufacturer. To solve this incident check:
1. Verify if the Air unit is powered. To do this, check the thermostat of the AC unit is ON.
2. Verify the AC unit operates properly by itself. To do this, disconnect the A/C unit Airzone system and select the unit
from the thermostat from the A/C unit.
3. Connection: Check the polarity and connection of the gateway connectors and the indoor unit. See the technical sheet
of the gateway in question.
4. Wiring: In DIN-rail gateways, check that the voltage between the poles (A/ -) and (B/ -) is correct (1.8 Vdc).
5. Verify the status of the LEDs of the gateway is correct. To do this check the self-diagnose section or the technical sheet
of the gateway.

Table of Contents

Other manuals for Airzone FLEXA 3.0 IBPRO6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Airzone FLEXA 3.0 IBPRO6 and is the answer not in the manual?

Airzone FLEXA 3.0 IBPRO6 Specifications

General IconGeneral
BrandAirzone
ModelFLEXA 3.0 IBPRO6
CategoryThermostat
LanguageEnglish

Related product manuals