Communication instructions Chapter 9
Rockwell Automation Publication 2080-RM001D-EN-E - February 2015 187
Structured Text (ST)
CIPSYMBOLICCFG data type
The following table describes the CIPSYMBOLICCFG data type.
Parameter Data type Description
Service USINT Service code:
0 - Read (default)
1 - Write
Symbol STRING Name of the variable to Read/Write.
Maximum of 80 characters.
Field cannot be empty.
See Symbolic Read/Write syntax on page 188.
Count UINT Number of variable elements to Read/Write:
Valid values: 1 - 490
1 is used if the value is set to 0.
Type User-defined User-defined data type for the target variable.
See Symbolic data type support on page 187.
Offset USINT Reserved for future use.
A byte offset of Read/Write variable used to Read/Write a large size variable that cannot be processed in one
message.
0 0xFF
Reserved for future use.