EasyManua.ls Logo

Allen-Bradley Micro800

Allen-Bradley Micro800
652 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 12 Data conversion instructions
294 Rockwell Automation Publication 2080-RM001D-EN-E - February 2015
ANY_TO_USINT converts a value to an Unsigned Short Integer value.
Arguments
Parameter Parameter Type Data Type Description
EN Input BOOL Function enable.
When Enable = TRUE, execute the conversion to the 8-bit Unsigned
Short Integer computation.
When Enable = FALSE, there is no computation.
Applies only to LD programs.
i1 Input BOOL - SINT - BYTE - INT - UINT -
WORD - DINT - UDINT - DWORD -
LINT - ULINT - LWORD - REAL -
LREAL - TIME - DATE - STRING
Any non-Short Integer value.
o1 Output USINT An Unsigned Short Integer value.
ENO Output BOOL Enable out.
Applies only to LD programs.
ANY_TO_USINT operator ST language example
(* ST Equivalence: *)
bres := ANY_TO_USINT (true);
(* bres is 1 *)
tres := ANY_TO_USINT (t#0s46ms);
(* tres is 46 *)
mres := ANY_TO_USINT ('0198');
(* mres is 198 *)
ANY_TO_USINT