EasyManua.ls Logo

Allen-Bradley Micro800 - Tonoff

Allen-Bradley Micro800
652 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Timer instructions Chapter 23
Rockwell Automation Publication 2080-RM001D-EN-E - February 2015 625
TONOFF delays turning on an output on a true rung, then delays turning off the
output on the false rung.
Arguments
Parameter Parameter type Data type Description
IN Input BOOL If Rising Edge (IN) turns from 0 to 1, the On-delay timer starts.
If the Programmed On-delay time is elapsed and the Falling Edge (IN) turns
from 1 to 0, the Off-delay timer starts and resets the elapsed time (ET).
If the Programmed On-delay time is elapsed and the Falling Edge (IN) turns
from 1 to 0, the Off-delay timer starts. If the Programmed On-delay time is
not elapsed and the Rising Edge (IN) turns from 0 to 1, the On-delay timer
starts.
PT Input TIME On-delay time setting.
PTOF Input TIME Off-delay time setting.
Q Output BOOL If TRUE, the Programmed On-delay time is elapsed and Programmed Off-
delay time is not elapsed.
ET Output TIME Current elapsed time. Possible values range from 0ms to 1193h2m47s294ms.
If the Programmed On-delay time is elapsed and the Off-delay timer is not
starting, the elapsed time (ET) remains at the on-delay (PT) value. If the
Programmed Off-delay time is elapsed and the Off-delay timer is not starting,
the elapsed time (ET) remains at the off-delay (PTOF) value until the rising
edge occurs again.
Tip: If you use the EN parameter with this block, the timer starts incrementing
when EN is set to TRUE, and continues to increment even if EN is set to FALSE.
TONOFF

Table of Contents

Other manuals for Allen-Bradley Micro800

Related product manuals