Chapter 9 Communication instructions
246 Rockwell Automation Publication 2080-RM001D-EN-E - February 2015
Results
The Local Variables selector should look similar to the following image.
Configure initial values for TargetCfg
1. From the ladder diagram POU, double-click the A_TarCfg variable to open
the global variables selector.
2. Expand the TargetCfg parameter to view additional parameters.
3. Enter the following values in the Initial Value column for each parameter.
Parameter Initial value
A_TarCfg.Path '4,192.168.1.19'
A_TarCfg.CipConnMode 1
A_TarCfg.UcmmTimeout 0
A_TarCfg.ConnMsgTimeout 0
A_TarCfg.ConnClose Leave blank