User Manual    California Instruments 
CSW Series    31 
 
COLUMN 1: 
SIZE 
(AWG) 
COLUMN 2: 
AMPERES 
(MAXIMUM) 
COLUMN 3: 
OHMS/100 FEET
(ONE WAY) 
COLUMN 4: 
IR DROP/100 FEET
(COL. 2 X COL. 3) 
14 15  0.257  3.85 
12 20  0.162  3.24 
10 30  0.102  3.06 
8 40  0.064  2.56 
6 55  0.043  2.36 
4 70  0.025  1.75 
2 95  0.015  1.42 
1/0 125  0.010  1.25 
3/0 165  0.006  1.04 
Recommended Wire Gauge Selection Guide 
 
The output power cables must be large enough to prevent a total voltage drop exceeding 1% of 
the rated output voltage between the power source and the load.  Table 3-1 shows the AWG size 
of the cables that may be used.  Cable lengths must not exceed twenty-five (25) feet. For lengths 
greater than 25 feet, calculate the voltage drop from the following formula: 
 
  2 X DISTANCE X CABLE RESISTANCE PER FT. X CURRENT = VOLT DROP 
 
 
LOAD CURRENT  WIRE GAGE 
22 AMPS  10 AWG 
37 AMPS  8 AWG 
74 AMPS  4 AWG 
111 AMPS  2 AWG 
Table 3-1:  Wire Sizes