LCX 890 Installation Guide 3
Controller Dimensions and Weight
Each LCX 890 is 34.9H × 18.3W × 4.67D in. (886.46H × 464.82W ×
118.62D mm) and weighs 38 lbs (14.17 kg) without relays.
Each LCX 898 is 38.8H × 27.35W × 4.67D in. (985.52H × 694.69W ×
118.62D mm) and weighs 42 lbs (23.49 kg) without relays.
Power Requirements
Caution
Any LCX 890 should receive power from its own independent,
unswitched circuit.
You can select an AC line voltage of 115 V, 230 V, or 277 V. You re-
ceive the controller set to 115 V. Instructions for selecting the AC line
voltage you want are included with the installation.
Voltages you can select are as follows (each uses a 2 A slow blow fuse):
115 VAC +/– 10% 50/60 Hz
230 VAC +/– 10% 50/60 Hz
277 VAC +/– 10% 50/60 Hz
Each LCX 890 series controller consumes 115 VA of power.
Cable Limitations
The maximum cable length for all buses is 4,000 ft (1219 m) at 19,200
baud (up to 32 Infinet controllers). You can extend buses beyond
4,000 ft (1219 m) or put more than 32 Infinet controllers on less than
4,000 ft (1219 m) by using the InfiLink 200 amplification module.