48 LCX 890 Installation Guide
Figure 7 shows a wiring diagram for a four-wire momentary switch to
control four adjacent outputs on an LCX 898. This way you can have a
“master” switch for the four areas.
Figure 25. Wiring Diagram for Four-Wire Momentary Switch
Controlling Four Adjacent Outputs (LCX 898 Only)
If you wire momentary switches this way, the length of wire required
varies depending on the number of adjacent outputs you wire to the
switch.
Table 8 shows the correct maximum wire length for two, three, and four
adjacent relays.
Table 8. Lengths of Wire Required for Wiring
Adjacent Outputs to the Same Switch
No. Relays Maximum Wire Length
2 750 ft (228.6 m)
3 450 ft (137 m)
4 325 ft (99 m)
RED (ON)
WHT
BLK (OFF)
YEL
First Output
Terminal Block
Second Adjacent
Output Terminal
Block
Third Adjacent
Output Terminal
Block
Fourth Adjacent
Output Terminal
Block