RecommendedCableSizes
WARNING:At100%switchmodeload,theneutralmustberatedfor200%phase
current.
Caution:Allwiringmustcomplywithallapplicablenationaland/orelectricalcode.
Note:Therecommendedcablesizesarebasedonanenvironmentwithanambient
temperatureof30°C(86°F).Usestrandedcoppercables.
10kV A15kV A20kV A30kV A
Utility/mainsinput
8AWG6AWG4AWG1AWG
Staticbypassinput
8AWG6AWG4AWG1AWG
DCinput
1AWG1AWG1AWG1AWG
Output8AWG6AWG4AWG1AWG
ConnectionTerminals
Cablesize(A WG)CablelugtypeCrimpingtoolDieTerminalbolt
diameter
12YA12CL2TC38MD7-34RW12CVT
6mm(0.2in)
8YA8CL2TC38MD7-34RW8CVT
6mm(0.2in)
6YA6CL2TC38MD7-34RW6CVT
6mm(0.2in)
4YA4CL2TC38MD7-34RW4CVT
6mm(0.2in)
1YA1CL2TC38MD7-34RW1CVT
6mm(0.2in)
TorqueSpecications
Thepowerwiringshouldbetorquedto7Nm(45lbf-in).
4
Smart-UPS™VT10–30kV A208/220VSingleandParallelInstallation
990–1598E-001