Specications
WARNING:TheUPSmustbesuppliedfroma208/120Vor220/127V4W+GND
60HZsource.
ACInputSpecications
10kV A15kV A20kV A30kV A
208V220V208V220V208V220V208V220V
Connectiontype4-wire(3PH+N+G)
Inputfrequency
(Hz)
40-70
Ithd<5%atfullload
Nominputcurrent
(A)
24.323.036.634.648.645.873.269.0
Maxinputcurrent
(A)
26.725.240.238.053.050.180.175.8
Inputcurrent
limitation(A)
32.832.849.549.565.265.298.898.8
Inputpowerfactor
correction
>0.98atload>50%
MaximumShort
CircuitWithstand
(kA)
30
ACBypassInputSpecications
10kV A15kV A20kV A30kV A
208V220V208V220V208V220V208V220V
Connectiontype4-wire(3PH+N+G)
Inputfrequency
(Hz)
50+/-10or60+/-10
Nominputcurrent
(A)
27.826.241.639.4
55.5
52.583.378.7
2
Smart-UPS™VT10–30kV A208/220VSingleandParallelInstallation
990–1598E-001