MinimumBreakerSettings
800%overload
bypass
operation
150%overload
normal/battery
operation
125%overload
normal/battery
operation
Continuously
Duration500ms60s10min
Mainsinput
-
1
--
34A
Staticbypass
input
223A
--
31A
10kV A
UPSoutput223A42A35A31A
Mainsinput
-
1
--
51A
Staticbypass
input
333A
--
46A
15kV A
UPSoutput333A63A52A46A
Mainsinput
-
1
--
68A
Staticbypass
input
444A
--
62A
20kV A
UPSoutput444A84A70A62A
Mainsinput
-
1
--
99A
Staticbypass
input
667A
--
92A
30kV A
UPSoutput667A125A105A92A
1
Forsinglemainssystems,usethehighervalueofmainsandstaticbypass
990–1598E-001
Smart-UPS™VT10–30kV A208/220VSingleandParallelInstallation