ConnecttheACInputandACOutputCables
WARNING:UseONLYcompressiontypelugs.Donotloosenoraddcablestoany
factorypreinstalledcablesonbusbars.Usetheupperfrontpartofbusbarfor
connectiononly.
Note:Theterminalsareonlysuitableforconnectionofcoppercables.
SingleMains
1.ConnecttheACinputcablesandtheneutralto
theinputcablelandings.
2.ConnecttheACoutputcablesandtheneutral
totheoutputcablelandings.
3.Connectthegroundcablestothestuds(earth
symbolbeneath)usingascrew.
DualMains
1.RemovethethreebusbarsA,B,andCby
removingtwoM6screwsfromeachbusbar.
30
Smart-UPS™VT10–30kV A208/220VSingleandParallelInstallation
990–1598E-001