ConnecttheACInputandACOutputCables
WARNING:UseONLYcompressiontypelugs.Donotloosenoraddcablestoany
factorypreinstalledcablesonbusbars.Usetheupperfrontpartofbusbarfor
connectiononly.
Note:Theterminalsareonlysuitableforconnectionofcoppercables.
SingleMains
1.ConnecttheACinputcablesandtheneutralto
theinputcablelandings.
2.ConnecttheACoutputcablesandtheneutral
totheoutputcablelandings.
3.Connectthegroundcablestothestuds(earth
symbolbeneath)usingascrew.
1
2
3
DualMains
1.RemovethethreebusbarsA,B,andCby
removingtwoM6screwsfromeachbusbar.