IMPORTANTSAFETYINSTRUCTIONS—
SAVETHESEINSTRUCTIONS
WARNING:ALLsafetyinstructionsintheSafetySheet(990-2822)mustberead,
understoodandfollowedwheninstallingtheUPSsystem.Failuretodosocouldresult
inequipmentdamage,seriousinjury,ordeath.
WARNING:AftertheUPShasbeenelectricallywired,donotstartitup.Start-upis
commissionedtoAPCauthorizedpersonnelonly.
WARNING:WhentheUPSinputisconnectedthroughexternalisolatorsthat,when
opened,isolatetheneutral,orisconnectedtoanITpowerdistributionsystem,alabel
mustbettedattheUPSinputterminalsbytheUPSsupplier,andonallprimary
powerisolatorsinstalledremotefromtheUPSareaandonexternalaccesspoints
betweensuchisolatorsandtheUPSbytheuser,displayingthefollowingtext(or
equivalent):"Riskofvoltagebackfeed.Beforeworkingonthiscircuit,isolatetheUPS
andcheckforhazardousvoltagebetweenallterminalsincludingtheprotectiveearth."
Caution:Allelectricalpowerandpowercontrolwiringmustbeinstalledbyaqualied
electrician,andmustcomplywithlocalandnationalregulationsformaximumpowerrating.
Caution:Waituntilthesystemisreadybepoweredupbeforeinstallingbatteries.Failure
todosocanresultinadeepdischargeofthebatteriesandcausepermanentdamage(the
timefromthebatteryinstallationtimetilltheUPSispoweredupshouldnotexceed72
hoursor3days.
Note:ThesystemisdesignedforconnectiontoanITpowerdistributionsystem.
Note:Theparallelcablesmustberunbytheelectricianbutnotattached.Theeldservice
engineerfromSchneiderElectricwillinstalltheparallelcommunicationboxandattachall
cablestotheUPSunits.
Note:Ensurethattheunitisinitsnallocationpriortoinstallation.
Note:Batteryandutilitypowermustnotbeconnecteduntilallotherwiringhasbeen
completed.