CS175-275-575-875 Installation Guide 71
5
On: enables end download report.
6
On: enables sensor low battery report.
7
On: enables sensor missing report.
8
On: enables automatic test reporting only when system is
armed.
Segment 5 1
On: enables lost clock service LED.
2
On: enables all abort.
3-8
Reserved
Location 52 System timers (14 segments, ND)
This location contains the duration of various system timing functions.
Segment 1
Dynamic battery test duration. 0 to 255 minutes. 0 = no test.
Segment 2
Mains fail report delay. 0 to 255 minutes.
Segment 3
Power up delay. 0 to 60 seconds. 0 = no power up delay.
Segment 4
Internal Siren time. 1 to 255 minutes.
Segment 5
Telephone line cut delay. 0 to 255 seconds. 0= no telephone line
monitoring.
Segment 6
B-Alarm timer
Segment 7
Chime time in 50 msec. (1/20th second) increments from 0-12
seconds. 0 = follows zone.
Segment 8
Fire alarm verification time. 120 to 255 seconds. 0 = no fire alarm
verification.
Segment 9
Zone activity monitor. 0 to 255 days. 0= disabled.
Segment 10
Double Knock Time. Min, ½ min resolution.
Segment 11
Double Knock Open Time. 10 to 255 seconds.
Segments 12
External siren time. 1 to 255 minutes.
Segments 13-
14
Reserved
Location 53 Special features (one segment, FSD)
Segment 1 1
On: enables the six-digit code location. If the six-digit location is
enabled, all arm/disarm codes and the Go to program code are
six digits. If this option is enabled, the default user 1 code is
112256.
If you enable this location, verify that the Go to program code is
a six-digit code before exiting programming.
2
On: requires code entry for
98
(perform call back download)
and 99 (answer incoming call for download) functions.