ATI Model F12/D Gas Transmitter Part 4 – Operation
58
O&M Manual (Rev-H)
Alarm Test Menu
The Alarm Test Menu can be used to test the gas level and Trouble alarms to
verify operation of the associated relays (see Relay Operation, Menus, and
Settings on page 70).
Devices wired to the relays may activate when
“Start” is selected. Inform all personnel before
performing the test.
Figure 73. Alarm Test Menu
Scroll up or down to specify which alarms to test -
C, W, A, T, and save the selection by pressing the
Enter key.
(C=Caution, W=Warning, A=Alarm, T=Trouble)
Select Start to begin the test.
Press any key to end the test. The test stops
automatically after 5 minutes.
Test
Warning: this wi
►Alarm= - - - -
Start
Test
Warning: this wi
►Alarm= - - A -
Start
Test
Warning: this wi
Alarm= - - A -
>Start
Test
Warning: this wi
Alarm= - - A -
Any key to STOP
Warning: this wi
►Alarm= C W A T
“This will activate alarm relays”