6.4 - List of parameters which can be set
Parameter N° Description Unit Range of setting
Factory
setting
P202
Maximum exterior temperature (warmest day for heat curve)
°C
11 to 25
20
P203
Minimum exterior temperature ( (coldest day for heat curve))
°C
-30 to 10
-5
P204
Summer/winter changeover: choice of changeover method
-
auto: changeover is done automatically based on the
exterior temperature
manu: changeover is done manually by the user
manu
P205
Summer/winter time delay: time period for observation
of the exterior temperature before automatic season
changeover. Only used if automatic changeover is activated.
hour
0 to 48
12
P206
Reactivity: the temperature for heating takes into account
the ambient temperature to accelerate heating time when
heating is switched on or restarted.
-
yes: reactivity activated
no: reactivity deactivated
no
P207
Anticipation of heating: heating restarted before return
from holidays (for getting a home already at the set
temperature on return)
-
yes: anticipation activated
no: anticipation deactivated
no
P208
Minimum exterior temperature for operation using only the
HP.
The back-up is authorised to operate in colder temperatures.
°C
P209 to 20
2
P209
Maximum exterior temperature for operation using only the
back-up.
The heat pump is authorised to operate in warmer
temperatures.
°C
-20 to P323
-20
P210
Operation in peak hours
(HP/HC contact open)
-
0: no operation allowed
1: HP limited to 1st power stage
2: HP limited to 2nd power stage
3: full HP without back-up
4: HP + 1 stage back-up (2kW)
5: HP + 2 stages back-up (4kW)
6: Full authorization: HP + 3 stages back-up (6kW)
7: back-up (6kW or boiler) without HP
8: anti-frost confort level
9: eco
10: do not use
6
P212
Type of back-up
-
no: no backup
Elec: electrical back-up
BOIL: back-up boiler
no
P213
Heat pump time-out: allows the heat pump to continue
running for a period of time after intervention of the back-
up
min.
1 to 20
5
P214
Di erence in temperature between the back-up and the
heat pump
°K
0 to 7
Elec : 4
BOIL : 7
P215
Presence of a heat pump
-
0: operation without heat pump
1: presence of a heat pump
1
P216 to p225
Not concerned
-
Do not change the setting
0.5
P221
Choice of heat pump 1 compressor in operation
-
0 to 2
0
P222
Choice of heat pump 2 compressor in operation
-
0 to 2
0
P223
Choice of heat pump 3 compressor in operation
-
0 to 2
0