Parameter N° Description Unit Range of setting
Factory
setting
P226
Choice for pressure sensor
0: no pressure sensor
1: IMIT/HUBA sensor (4 bar)
2: ELTEK sensor (4 bar)
3: 6 bar sensor
3
P227
Speed of heat pump circulator pump
%
10 to 100
100
P228
Post-circulation of the heat pump circulator pump
-
Do not change the setting
3
P230
Speed of heating circuit circulator pump
%
10 to 100
100
P231
Setpoint temperature for heating circuit
°C
auto: automatic set temperature from the air sensor or
exterior sensor (if connected)
or
20 to 70: setting  xed in °C
AUTO
P232
Setpoint temperature at the coldest day
°C
P233 to 70
70
P233
Setpoint temperature at the warmest day
°C
20 to P232
40
P234
Action of circulating pump for heating circuit
-
0: permanent
1: controlled by room temperature / room thermostat
2: controlled by room temperature with lower setpoint
when room temperature target is reached («anti-cold
radiators» function)
1
P235
Lowering of the Heating setpoint : lowering applied to
the heating temperature when room has reached the
temperature target
°K
0 to 30
4
P236
Lowering in ECO: temperature lowering applied to the
heating setpoint during ECO mode.
°K
0 to P237
10
P237
Lowering in Frost protection: temperature lowering applied
to the heating setpoint during Frost protection mode
°K
P236 to 40
20
P238
Self-adaptability: automatic correction of the heat curve
based on the room temperature on a 24h cycle
-
yes: correction activated
no: correction deactivated
no
P239
Complementary self-adaptability: automatic correction of
the temperature on a 3h cycle of room temperature
-
yes: correction activated
no: correction deactivated
no
P247
Room temperature hysteresis (requires an room
temperature sensor) : room temperature deviation
triggering a heating demand
°K
0,1 to 1
0,5
P250
Circuit 2 - Circulator speed
(in case of 2nd heating circuit kit)
%
10 to 100
100
P251
Circuit 2 - Setpoint temperature for heating circuit
°C
auto: automatic setpoint from air or outside probe if
connected
or
20 to 70:  xed set point in°C
AUTO
P252
Circuit 2 - Setpoint temperature at the coldest day
°C
P253 to 70
70
P253
Circuit 2 - Setpoint temperature at the warmest day
°C
20 to P252
40
P254
Circuit 2 - Action of circulating pump for heating circuit
-
0: permanent
1: controlled by room temperature / room thermostat
2: controlled by room temperature with lower setpoint
when room temperature target is reached («anti-cold
radiators» function)
1
P255
Circuit 2 - Lowering of heating setpoint : lowering applied
to the heating temperature when room has reached the
temperature target
°K
0 to 30
4