- 6P10 PILOT MANUAL
-
24
Parameter N° Description Unit Range of setting
Factory
setting
P256
Circuit 2 - Lowering in ECO: temperature lowering applied to
the heating setpoint during ECO mode.
°K
0 to P257
10
P257
Circuit 2 - Lowering in Frost protection: temperature
lowering applied to the heating setpoint during Frost
protection mode
°K
P256 to 40
20
P258
Circuit 2 - Self-adaptability: automatic correction of the heat
curve based on the room temperature on a 24h cycle
-
oui: correction enabled
non: correction disabled
non
p259
Circuit 2 - Complementary self-adaptability: automatic
correction of the temperature on a 3h cycle of room
temperature
-
oui: correction enabled
non: correction disabled
non
P267
Circuit 2 - (mixed circuit option) - Room temperature
hysteresis (requires a room sensor): room temperature
deviation triggering a heating demand
°K
0,1 to 1
0,5
P271
Domestic sharing: simultaneous operation of heating and
domestic hot water production at the end of the tank’s
heating cycle. Increases the available heating time for
installations with a larger volume of domestic hot water.
-
yes: sharing activated
no: sharing deactivated
no
P272
Anti-legionellosis – activation and choice of frequency: the
cycle raises the temperature in the domestic hot water tank.
This cycle eliminates the bacteria through thermal shock.
-
0: protection deactivated
1: (monthly): the cycle is carried out at the beginning of
each month, on the rst day P273 of the month
2: (weekly): the cycle is carried out each week on day P273
0
P273
Anti-legionellosis – choice of day to carry out anti-
legionellosis cycle
-
1(Monday) to 7 (Sunday)
2
P275
Circulating pump speed during production of domestic hot
water
%
10 to 100
100
P278
Lowering of the domestic hot water temperature in ECO
mode.
°K
0 to 40
10
P279
Maximum heating time of the domestic hot water tank (too
long heating time function)
min.
5 to 60
20
P281
Domestic hot water hysteresis : temperature drop in the
domestic hot water tank to start a new heating cycle
°K
2 to 15
5
P282 to p291
Not concerned
-
Do not change the setting