7. Indications
7.1. Indication lights
Figure 30: Local controls with indication lights
[1] illuminated (default: green): End position OPEN reached
[2] illuminated (default: red): Collective fault signal
[3] illuminated (default: yellow): End position CLOSED reached
Information
The three indication lights can be provided in different colours (deviating from the
standard).
Collective fault signal
The collective fault signal [2] appears if one of the following events occurs (default
configuration):
Torque fault: The set torque was exceeded before reaching an end position.
(This signal can be activated/deactivated via a switch in the controls.)
Thermal fault: Motor protection has tripped, i.e. the motor is overheated.
Phase failure: One phase is missing (3-ph AC motors only).
PTC tripping device:Test complete
Running indication
If the actuator is equipped with a blinker transmitter (wiring diagram designation:
S5), indication lights [1] and [3] can be used as running indication. The running
indication can be activated/deactivated via a switch in the controls. If the running
indication is active, the respective indication light blinks during operation.
7.2. Optional indications
7.2.1. Mechanical position indication via indicator mark
Figure 31: Mechanical position indicator
[1] End position OPEN reached
[2] End position CLOSED reached
[3] Indicator mark at cover