EasyManuals Logo

AUMA AM 01.1 User Manual

AUMA AM 01.1
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
3. Connect lower setpoint to customer connection XK (terminals 2/3). The lower
setpoint (0 V, 0 mA or 4 mA) is indicated on the label [5].
4. If the red LED [V10] E1/E2 <4 mA is illuminated:
4.1 Verify polarity of setpoint E1.
4.2 Check whether external load is connected to customer connection XK
(terminals 23/24) (observe max. load R
B
), or
4.3 Connect terminals 23/24 across customer connection XK (terminals 23/24).
5. Measure setpoint E1: Connect measuring device for 0 5 V to measuring points
[MP3/MP4].
For a setpoint E1 of 0 V or 0 mA, the voltmeter shows 0 V.
For a setpoint E1 of 4 mA, the voltmeter shows 1 V.
6. If measured value is not correct: Correct setpoint E1.
7. Measure actual value E2: Connect measuring device for 0 5 V to measuring
points [MP1/MP2].
For an actual value E2 of 0 mA, the voltmeter shows 0 V.
For an actual value E2 of 4 mA, the voltmeter shows 1 V.
8. If measured value is not correct: Re-set potentiometer or electronic position
transmitter and perform adjustment once again, starting from step 1.
9. Adjust positioner using potentiometer 0 [P3].
9.1 If both LEDs are OFF or the green LED [V28] is illuminated:Turn poten-
tiometer 0 [P3] slightly clockwise until the yellow LED [V27] is illuminated.
9.2 If the yellow LED [V27] is illuminated:Turn potentiometer 0 [P3] counter-
clockwise until the yellow LED [V27] goes out.Then turn potentiometer 0
[P3] slightly clockwise until the yellow LED [V27] is illuminated again.
Figure 49: Electronic positioner board
[P3] Potentiometer 0
[P4] Potentiometer max
[V27] Yellow LED: End position CLOSED reached
[V28] Green LED: End position OPEN reached
The setting is correct if the yellow LED [V27] is switched on when reaching end
position CLOSED.
End position OPEN
10. Move valve to end position OPEN.
11. Measure actual value E2 (measuring points [MP1/MP2]):
For an actual value E2 of 20 mA, the voltmeter shows 5 V.
12. If measured value is not correct: Re-set potentiometer or electronic position
transmitter and perform adjustment once again, starting from step 1.
13. Set maximum setpoint E1 (5 V or 20 mA, refer to label [5]).
14. Measure setpoint E1 (measuring points [MP3/MP4]):
For a setpoint E1 of 5 V or 20 mA, the voltmeter shows 5 V.
15. If measured value is not correct: Verify setpoint E1.
57
SA 07.2 SA 16.2 /SAR 07.2 SAR 16.2
AM 01.1/AM 02.1 Commissioning controls settings

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA AM 01.1 and is the answer not in the manual?

AUMA AM 01.1 Specifications

General IconGeneral
BrandAUMA
ModelAM 01.1
CategoryController
LanguageEnglish

Related product manuals