EasyManuals Logo

AUMA AM 02.1 User Manual

AUMA AM 02.1
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #61 background imageLoading...
Page #61 background image
Table 22: Further possible settings
[S27]Signal type
1)
Behaviour on loss of signal of
DIP 1 2 3 4Actual value E2Setpoint E1E2E1
0 5 V4 20 mAFail openFail as is
0 5 V4 20 mAFail openFail close
4 20 mA0 20 mA
0 20 mA
0 5 V
0 20 mA
0 5 V
0 10 V
4 20 mA0 20 mA
0 5 V
Fail close
4 20 mA0 20 mA
0 10 V
Fail as is
0 20 mA
0 5 V
4 20 mAFail open
in case of a signal loss, a misinterpretation might be made for 0 20 mA, 0 5 V or 0 10 V, due
to the fact that E1 or E2 could take the value 0 mA even without loss of signal (end position CLOSED
= 0 mA or 0 V).
1)
11.7.3. Adjustment in end positions
The setting described below applies to the standard positioner version, i.e. maximum
setpoint E1 (20 mA) triggers a travel to end position OPEN, minimum setpoint (0/4
mA) triggers a travel to end position CLOSED.
Figure 62: Electronic positioner board
[MP1] Measuring point () for actual value E2
[MP2] Measuring point (+) for actual value E2
[MP3] Measuring point (+) for setpoint E1
[MP4] Measuring point () for setpoint E1
[5] Label with signal indication
[V10] Red LED: E1/E2 <4 mA
End position CLOSED
1. Set selector switch to position Local control (LOCAL).
2. Move valve to end position CLOSED.
61
SA 25.1 SA 48.1 / SAR 25.1 SAR 30.1
AM 02.1 Commissioning controls settings

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA AM 02.1 and is the answer not in the manual?

AUMA AM 02.1 Specifications

General IconGeneral
BrandAUMA
ModelAM 02.1
CategoryController
LanguageEnglish

Related product manuals