PLC Errors for GE SNPX Protocol (Minor-Major) (cont’d)
Panel Error Code
P499 Hex Value
Description
0x8D0A Bad DOS Version. Must have DOS 2.0, or later, to support the SNP DOS Driver.
0x8E0A PC Serial port configured for SNP Master driver is not open; no communication can take place.
0x8F0A Out–of–Sequence SNP message. SNP message type received was not the type expected.
0x900A
Bad SNP BCC encountered. Transmission was aborted after maximum retries due to a bad Block Check
Code.
0x910A
Bad SNP communication. Transmission was aborted after maximum retries due to serial errors (that is,
parity, overrun, or framing errors).
0x920A
No SNP communication. Either communication has been lost or a communication session has not been
established.
0xC105 Invalid block state transition.
0xC205 The OEM key is NULL (inactive).
0xC305 Text length does not match traffic type.
0xC405 Verify with FA Card or EEPROM failed.
0xC505 No task–level Rack/Slot configuration to read or delete.
0xC605 Control Program (CP) tasks exist but requestor not logged into main CP.
0xC705 Passwords are set to inactive and cannot be enabled or disabled.
0xC805 Password(s) already enabled and can not be forced inactive.
0xC905 Login using non–zero buffer size required for block commands.
0xCA05 Device is write–protected.
0xCB05 A comm or write verify error occurred during save or restore.
0xCC05 Data stored on device has been corrupted and is no longer reliable.
0xCD05 Attempt was made to read a device but no data has been stored on it.
0xCE05 Specified device has insufficient memory to handle request.
0xCF05 Specified device is not available in the system (not present).
0xD005 One or more PLC modules configured have unsupported revision.
0xD105 Packet size or total program size does not match input.
0xD205 Invalid write mode parameter.
0xD305 User Program Module (UPM) read or write exceeded block end.
0xD405 Mismatch of configuration checksum.
0xD505 Invalid block name specified in datagram.
0xD605 Total datagram connection memory exceeded.
0xD705 Invalid datagram type specified.
0xD805 Point length not allowed.
0xD905 Transfer type invalid for this Memory Type selector.
0xDA05 Null pointer to data in Memory Type selector.
0xDB05 Invalid Memory Type selector in datagram.
0xDC05 Unable to find connection address.
0xDD05 Unable to locate given datagram connection ID.
0xDE05 Size of datagram connection invalid.
0xDF05 Invalid datagram connection address.