BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 54 Autronica Fire and Security AS
D.1.2 Prewarning
Prewarning from the BS-100 control panel is only registered on the BS-100
control panel. There will be no display on the BS-60 control panel(s).
Prewarning from a BS-60 control panel is registered on the relevant BS-60
control panel and on the BS-100 control panel.
There will be no display of info. on any other BS-60 control panel.
D.1.3 Fault
(The BS-100 control panel will look at the BS-60 control panels as ordinary
loops).
Fault from the BS-100 control panel is registered on the BS-100 control
panel. There will be no display of info. on BS-60 control panel(s).
Fault from a BS-60 control panel is registered on the relevant BS-60 control
panel and on the BS-100 control panel.
D.1.4 More alarms
More alarms from the BS-100 control panel will only be registered on the
BS-100 control panel. There will be no display of info. on the BS-60
control panel(s).
More alarms from a BS-60 control panel will also be registered as more
alarms on the BS-100 control panel. There will be no display of info. on
other BS-60 control panels.
2 alarms from 2 different BS-60 control panels will be registered as more
alarms on the BS-100 control panel.