BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 55 Autronica Fire and Security AS
D.2 Operating
D.2.1 Sounder Silence
The "SOUNDER SILENCE" function will be dependent upon how it is
configured within each of the BS-60 control panels.
When operating the "SOUNDER SILENCE" on the BS-100 control panel,
all alarm devices will be switched off (also devices connected to the BS-60
control panels).
If the "SOUNDER SILENCE" function is set to "OFF", the "SOUNDER
SILENCE" can only be operated from the BS-100 control panel.
If the "SOUNDER SILENCE" function is set to "ON", the "SOUNDER
SILENCE" can be operated from both the BS-60 and the BS-100 control
panel.
If the "SOUNDER SILENCE" is operated from a BS-60, alarm devices
connected to the BS-60 control panel which is operated, will be switched
off.
D.2.2 Reset
The "RESET" function will also be dependent upon how it is configured
within each of the BS-60 control panels.
When operating the "RESET" from the BS-100 control panel, the entire
system will be reset.
If the "RESET" function is set to "OFF", the "RESET" can only be operated
from the BS-100 control panel.
If the "RESET" function is set to "ON", the "RESET" can be operated from
both the BS-100 and the BS-60 control panel.
When operating the "RESET" from the BS-60 control panel, only the BS-60
which is operated will be reset.