BS100 DYFI Operators handbook
P-BS100/FE - Rev.F / Doc/ 980114 56 Autronica Fire and Security AS
D.3 Disable / Restore
When disabling on a BS-60 control panel, the "FUNCTION DISABLED"
indication lamp will light only on this control panel.
This will be logged in "SHOW-STATUS DISABLEMENTS" and in
"STORED-EVENTS" only on the current control panel.
It is advisable to disable / restore BS-60 addresses from the BS-100.
D.3.1 Address
The BS-100 can disable/restore all addresses in the system.
The BS-60 can only disable/restore addresses connected to it.
D.3.2 Zone
Only zones defined in the BS-100 control panel can be disabled/restored
from the BS-100 control panel. Zones defined in a BS-60 control panel can
be disabled/restored only at the relevant BS-60 control panel.
D.3.3 Controls
Controls connected to the BS-100 control panel can only be
disabled/restored from the BS-100 control panel.
Controls connected to the BS-60 control panel can only be disabled/restored
at the relevant BS-60 control panel.
D.3.4 Sounders
Sounders connected to the BS-100 control panel can only be
disabled/restored from the BS-100 control panel.
Sounders connected to a BS-60 control panel can only be disabled/restored
at the relevant BS-60 control panel
D.3.5 Fire brigade / fighters
BMA, BMF, BMFO outputs from the BS-100 control panel can only be
disabled/restored from the BS-100 control panel.
BMA, BMF, BMFO outputs from the BS-60 control panel can only be
disabled/restored at the relevant BS-60 control panel.