C - INSTALLATION
2.1 - MAXIMUM OPENING ANGLE
The installation of the actuators depends on the desired opening angle which depends on distance D (the
distance between the axis of the hinge and the inner side of the post).
Normal case
• If D<170mm
D
D
distance D
view from above
post
Special cases
If D>170mm and if the structure of the posts allows, the posts must be cut so that D is equal to 170mm.
D’
post
• If D <0mm, place a shim thick enough so that D is equal to 0mm.
D’
post
Determine the opening angle of each panel based on the data in the following table.
The opening angle may be different for each panel but must never be less than 40°.
For
opening up to
Distance D
(in mm)
90° from 0 to 170 max
100° from 0 to 110 max
110° from 0 to 60 max
120° from 0 to 20 max
D
D
central stop
Inner side of the property
view from above
opening
angle
opening
angle
side
stop