5-97
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
MV display setup
The MV related items to be displayed in the operation display mode can be set.
Item (Bank) Display Contents Initial value User level
MV display setup
(Setup bank)
Whether or not the MV value related items
are displayed in the operation display
mode is determined by the sum of the
following weights:
Bit 0: MV display
Disabled: 0, Enabled: +1
Bit 1: Heat MV/cool MV display
Disabled: 0, Enabled: +2
Bit 2: MFB display
Disabled: 0, Enabled: +4
Bit 3: AT progress display
Disabled: 0, Enabled: +8
15 Standard,
High function
AT progress display
MFB display
MV display
2
3
2
2
2
1
2
0
• When using the SLP-C35 Smart Loader Package, not only the numeric value, but
also the bit input can be used to set [
C75
: MV display setup].
Handling Precautions
• Even though the heat MV/cool MV display is set at [Enabled], the heat
MV/cool MV is not displayed when [
C26
: Heat/Cool control] is set at “0”
(Disabled).
• Even though the AT progress display is set at [Enabled], the AT progress is
not displayed while the AT is stopping.
• Even though the MFB display is set at [Enabled], the MFB is not displayed
if the model does not provide the position proportional output.