Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
CT input current value display setup
The CT current value to be displayed in the operation display mode can be set.
Item (Bank) Display Contents Initial value User level
CT input current value
display setup
(Setup bank)
0: CT current value is not displayed in the
operation display mode.
1: CT1 current value is displayed in the
operation display mode.
2: CT1 to 2 current values are displayed in
the operation display mode.
0 Standard,
High function
• When the optional model has two CT input points, the display and setting can be
made.
User level
The user level of the console display can be set.
As a larger value is set, the number of possible displays/settings is increased.
Item (Bank) Display Contents Initial value User level
User level
(Setup bank)
0: Basic configuration
1: Standard configuration
2: High function configuration
1 Basic,
Standard,
High function
LED monitor
The function of the decimal point LED at the right end digit of the lower display
(lower 4-digit display) can be set.
Item (Bank) Display Contents Initial value User level
LED monitor
(Setup bank)
0: Disabled
1: Flashing while data is being sent through
RS-485 communication.
2: Flashing while data is being received
through RS-485 communication.
3: Logical OR of all DI statuses
4: Flashing in READY mode
0 High function