6-20
Chapter 6. LIST OF DISPLAYS AND SETTING DATA
Display Item Contents
Initial
value
User
level
Notes
Internal Event
Configuration 3
Digits are assigned from right to left
in the order 1, 2, 3, 4.
0000 2
1st digit: Controller
alarm OR
0: None
1: Alarm direct + OR operation
2: Alarm direct + AND operation
3: Alarm reverse + OR operation
4: Alarm reverse + AND operation
2nd digit: Special
OFF setup
0: As usual.
1: When the event set value (main
setting) is “0”, the event is “OFF”.
3rd digit: Delay unit 0: 0.1 s
1: 1 s
2: 1 min
4th digit: Undefined. 0
Internal Event 2
Configuration 1
Operation type
Same as Internal Event 1
Configuration 1.
0 0
Internal Event 2
Configuration 2
1st digit: Direct/ Reverse
2nd digit: Standby
3rd digit:
EVENT state
at READY
4th digit: Undefined.
Same as Internal Event 1
Configuration 2.
0000 0
Internal Event 2
Configuration 3
1st digit: Controller alarm OR
2nd digit: Special OFF setup
3rd digit: Delay unit
4th digit: Undefined.
Same as Internal Event 1
Configuration 3.
0000 2
Internal Event 3
Configuration 1
Operation type
Same as Internal Event 1
Configuration 1.
0 0
Internal Event 3
Configuration 2
1st digit: Direct/ Reverse
2nd digit: Standby
3rd digit: EVENT state
at READY
4th digit: Undefined.
Same as Internal Event 1
Configuration 2.
0000 0
Internal Event 3
Configuration 3
1st digit: Controller
alarm OR
2
nd digit: Special OFF setup
3rd digit: Delay unit
4th digit: Undefined.
Same as Internal Event 1
Configuration 3.
0000 2
Internal Event 4
Configuration 1
Operation type
Same as Internal Event 1
Configuration 1.
0 0
Internal Event 4
Configuration 2
1st digit: Direct/ Reverse
2nd digit: Standby
3rd digit: EVENT state
at READY
4th digit: Undefined.
Same as Internal Event 1
Configuration 2.
0000 0
Internal Event 4
Configuration 3
1st digit: Controller
alarm OR
2nd digit: Special OFF setup
3rd digit: Delay unit
4th digit: Undefined.
Same as Internal Event 1
Configuration 3.
0000 2
Internal Event 5
Configuration 1
Operation type
Same as Internal Event 1
Configuration 1.
0 0
(Continue on next page.)

Table of Contents