EasyManua.ls Logo

Azbil C35 Series - Page 198

Azbil C35 Series
290 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-22
Chapter 6. LIST OF DISPLAYS AND SETTING DATA
DI Assignment bank
Bank selection:
Display Item Contents
Initial
value
User
level
Notes
Internal Contact 1
Operation type
0: No function
1: LSP group selection (0/+1)
2: LSP group selection (0/+2)
3: LSP group selection (0/+4)
4: PID group selection (0/+1)
5: PID group selection (0/+2)
6: PID group selection (0/+4)
7: RUN/READY selection
8: AUTO/MANUAL selection
9: LSP/RSP selection
10: AT Stop/Start
11: Invalid
12: Control action direct/reverse
selection (As setting/opposite
operation of setting)
13: SP RAMP enabled/disabled
14: PV Hold (No-hold/Hold)
15: PV maximum value hold (No-
hold/Hold)
16: PV minimum value hold (No-
hold/Hold)
17: Timer Stop/Start
18: Release all DO latches (Continue/
Release)
19: Advance (No-advance/Advance)
20: Step hold (No-hold/Hold)
0 0
Internal Contact 1
Input bit function
0: Not used (Default input)
1: Function 1 ((A and B) or (C and D))
2: Function 2 ((A or B) and (C or D))
3: Function 3 (A or B or C or D)
4: Function 4 (A and B and C and D)
0 2
When using internal contact
1, the default input is digital
input (DI) 1.
(Continue on next page.)

Table of Contents

Related product manuals