5-39
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
C0
1
(PV input range type)
C04
(Decimal point position)
SPU
(SP ramp up)
SPD
(SP ramp down)
2 (0 to 1200°C) Setting disabled 0.0 to 999.9 0.0 to 999.9
3 (0.0 to 800.0°C) 0 (No decimal point) 0.0 to 999.9 0.0 to 999.9
1 (1 digit after the decimal point) 0.00 to 99.99 0.00 to 99.99
88 (0 to 10V) 0 (No decimal point) 0.0 to 999.9 0.0 to 999.9
1 (1 digit after the decimal point) 0.00 to 99.99 0.00 to 99.99
2 (2 digits after the decimal point) 0.000 to 9.999 0.000 to 9.999
3 (3 digits after the decimal point) 0.0000 to 0.9999 0.0000 to 0.9999
The ramp is started assuming that the current PV value is used as start point
when the SP ramp-up or ramp-down is possible under the following conditions.
The power is turned ON.
READY+AUTO status is changed to RUN+AUTO status.
RUN+MANUAL status is changed to RUN+AUTO status.
The AT function is completed (both normal end and forced stop).
Example: (1) When READY is changed to RUN with SP=100°C, PV=25°C,
SPU=0.0, and SPd=1.0, the PV is not started.
(2) When READY is changed to RUN with SP=50°C, PV=100°C,
SPU=0.0, and SPd=1.0, the PV is started.
The SP ramp does not function for remote SP.
Handling Precautions
Before changing the slope of the SP ramp, make sure that SP ramping is not
in progress.
If the setting is changed while SP ramping is in progress, the SP may change
suddenly.