EasyManua.ls Logo

Azbil JTD910S - Page 114

Azbil JTD910S
196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-48
Chapter 3 Starting and Stopping this Device
Calculation example:
ρ: 0.9
ρ
0
: 0.935 (general-purpose remote)
l: 1500 mm
h: 250 mm
d: 500 mm
would result in:
0% liquid level differential pressure
LRV = 250×0.9 = 225 mm H
2
O = 2.206 kPa
100% liquid level differential pressure
URV = (1500+250)×0.9 = 1575 mm H
2
O = 15.45 kPa
Accordingly,
Low limit (URV): 2.206 kPa
High limit (URV): 15.45 kPa
is the resulting range.

Table of Contents

Related product manuals