3-58
Chapter 3  Starting and Stopping this Device
Calculation example:
ρ:  0.9
ρ
0
:  0.935 (general-purpose remote)
l:   1500 mm
h:  250 mm
d:  2000 mm
would result in:
0% liquid level differential pressure
        LRV = (250×0.9) - (2000×0.935)
  = -1645 mm H
2
O = -16.13 kPa
100% liquid level differential pressure
        URV = (1500+250)×0.9 - (2000×0.935) 
  = -295 mm H
2
O = -2.893 kPa
Accordingly,
        Low limit (LRV):   -16.13 kPa
        High limit (URV):   -2.893 kPa
is the resulting range.