4-19
Chapter 4  Maintenance and Troubleshooting of this Device
Table 4-5.  
HART7
Indicator 
Display
Diagnostics 
Display Message
Description Countermeasures
Maintenance 
Required
AL.28
SWITCH
External Zero/Span 
Adjustment Failure
External Zero/Span 
Adjustment Failure
There is a problem with the 
external zero adjustment 
switch or the printed circuit 
board.
Contact customer service.
AL.21
ZERO. CAL
Excess Zero 
Calibration Value
Excess Zero Calibration 
Value
Check that the input 
pressure is appropriate for 
the calibration value, and 
calibrate again.
AL.22
SPAN. CAL
Excess Span 
Calibration Value
Excess Span Calibration 
Value
AL.26
NO.CALIB
Not Calibrated Not Calibrated
Restart the calibration value 
at the time of shipping, or 
calibrate the high and low 
limits of the setting range.
AL.61
PRESS.FQ
Pressure Frequency 
Index Alarm
Pressure Frequency Index 
Alarm
Check operating conditions
AL.62
STD.DEV
Standard Deviation 
Alarm
Standard Deviation Alarm
AL.63
OOR.CNT
Out-of-Range 
Count Alarm
Out-of-Range Count Alarm