Shutdown, storage
Operation manual b maXX BM4100 (NWR)
Document no.: 5.04052.09
129
of 142
12
In case you want to dispose the device, additional data is available in chapter ZDisposal
from page 131.
12.5 Storage conditions
The device is maintenance-free. If you keep to the environmental conditions during the
entire period of storage, you can assume, that the device will not be damaged. In case
the environmental conditions during storage are not kept, you should assume that the de
-
vice is damaged after storage.
CAUTION!
Property damage because of incorrect storage conditions
Incorrect storage can damage/destroy the device.
Therefore:
Assure, that the environmental conditions are kept during the entire period of storage:
m Climatic category 1K4
m Temperature range -25 °C to +55 °C
CAUTION!
Recommissioning without forming of the capacitors.
From six months storage period on, the capacitors are destroyed during commission-
ing, if they are not formed beforehand
m Reform the DC link capacitors:
n by supplying the device ready-to-operate for at least one hour with supply volt-
age
n but do not transmit a pulse enable during this time.
m Consider, that it is imperative, to connect the accordingly prescribed line commu-
tating reactor for this forming procedure.Devices, where no line commutating reac-
tor is necessary can directly be supplied with mains voltage.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Baumuller b maXX 4100 Series and is the answer not in the manual?

Baumuller b maXX 4100 Series Specifications

General IconGeneral
BrandBaumuller
Modelb maXX 4100 Series
CategoryInverter
LanguageEnglish

Related product manuals