Installation
Operation manual b maXX BM4100 (NWR)
Document no.: 5.04052.09
79
of 142
7
Refer to ZInterface cable RS232– on page 248, if the cable is made by the customer.
1)
X3-1 and X3-2: not short-circuit proof
1)
X100-3 and X100-4: limited short-circuit proof, in case of short-circuit a current flow of 10 mA is possible
X1 (RS 232) Recom-
mended con-
nection cable
Connection
technology
Note
BM4135
BM4145
BM4163
LIYCY
6x2x0.14 mm
2
SUB-D, 9-pin available as cable set:
see ZInterface cable RS232– on page
115.
WARNING!
Risk of injury because of mechanical hazard!
If a PC is not connected via an isolated transformer, the machine can do unexpected
actions.
Therefore:
Connect the PC via an isolated transformer or use a battery operated PC (e. g. lap-
top, notebook) without connecting a charger.
NOTE!
In case you don’t use an optically decoupled interface cable, the cable shield has only
to be connected to the connector housing at the controller connector.
The company Baumüller Nürnberg GmbH recommends the usage of optically decou-
pled transmitters (e.g. from the company Ratioplast part No. 901SV232C6095 and
part No. 901SV232T6095)
X3 (SELV/PELV)
1)
Max. cable-Ø Connection technology Load capacity
BM4135
BM4145
BM4163
1.5 mm
2
plug-in contact X3-1, X3-2 and X3-6: 4.0 A
in case you consider UL
508 C: max. 1.0 A
X100 (SELV/PELV)
1)
max. cable-Ø Connection technology Load capacity
BM4135
BM4145
BM4163
1.5 mm
2
plug-in contact X100-1, X100-2, X100-5
and X100-6: 4.0 A