Integrated safety
EL72x1-901x 179Version: 1.9
Definition Description
RTSensor Reaction time of the sensor until the signal is provided at the interface. Typically supplied by
the sensor manufacturer.
RTInput Reaction time of the safe input, such as EL1904 or EP1908. This time can be found in the
technical data. In the case of the EL1904 it is 4 ms.
RTComm Reaction time of the communication This is typically 3x the EtherCAT cycle time, because
new data can only be sent in a new Safety-over-EtherCAT telegram. These times depend
directly on the higher-level standard controller (cycle time of the PLC/NC).
RTLogic Reaction time of the logic terminal. This is the cycle time of the logic terminal and typically
ranges from 500 µs to 10 ms for the EL6900, depending on the size of the safety project.
The actual cycle time can be read from the terminal.
RTOutput Reaction time of the output terminal. This typically lies within the range of 2 to 3 ms.
RTActor Reaction time of the servo terminal from the cut-off of the 24 V at the terminal point until the
safe cut-off of the gate driver (Under Voltage Lockout). This time is typically about 20 ms.
WDComm Watchdog time of the communication
This results in the following equation for the typical-case reaction time:
with, for example
Worst-case reaction time
The worst case reaction time is the maximum time required to switch off the actuator in the case of an error.
Fig.213: Worst-case reaction time
This assumes that a signal change occurs at the sensor and is transmitted to the input. A communication
error occurs at precisely the moment when the signal is to be transferred to the communication interface.
This is detected by the logic following the watchdog time of the communication link. This information should
then be transferred to the output, but a further communication error occurs here. This error is detected at the
output following the expiry of the watchdog time and leads to the switch-off.
This results in the following equation for the worst-case reaction:
with, for example

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Beckhoff EL72 1-901 Series and is the answer not in the manual?

Beckhoff EL72 1-901 Series Specifications

General IconGeneral
BrandBeckhoff
ModelEL72 1-901 Series
CategoryTouch terminals
LanguageEnglish

Related product manuals