EasyManua.ls Logo

BIFFI ICON 2000 - Page 37

Default Icon
292 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
37
© Copyright by BIFFI Italia. All rights reserved.
“ICON2000”
instruction and operating manual
Section 618/2 chapt. E
Section 618/2
The figure below shows the wiring diagram:
The "VIEW and SET-UP" features can
configure different options which are
described in chap. I, paragraph “POSITIONER”.
If the POSITIONER function is active the
alpha-numeric display indicates the value
of the position request in % (R%: xxx.x).
If the actuator is not provided with a lithium battery (or not supplied by the auxiliary
24VDC) and if the main voltage fails, the output 4-20mA maintains the last value. If the
actuator is moved by handwheel, the output 4-20mA will not be updated.
4-20mA analogue input
The 4-20mA analogue input is the position request R% signal and is used by the ICON2000
to position the valve in inching and modulating actuators. The “POSITIONER” routine
processes the input signal, compares the present actuator position % with the position
request R% and if the difference is greater than the dead band, the actuator is driven to
reach the requested position. 4mA corresponds to request R% = 0% = valve closed and
20mA corresponds to request R%= 100% = valve open. The relationship between position
and request signals can be reversed by the “Polarity” function. The 4-20mA input is
opto-coupled. The input impedance is less than 250 ohm. The loss of the 4-20mA input
signal is indicated as follows:
• Change-over of the monitor relay
• Alarm LED on
• List of ALARMS (see Section 3 chap.N, “Diagnostic messages”)
• Alarm log
37,5
NORMAL REMOTE
R:47% next?
Actuator terminals
cable
0Vdc
0V
4-20mA
B9
B8
GROUND
shield
4-20
mA
generator

Table of Contents

Related product manuals