“ICON 2000v4"
instruction and operating manual
© Copyright by BIFFI Italia. All right reserved. Section 618/42 Page 30
Contents may change without notice
12. GSD file
; GSD-File for ICON2000v4 BIFFI ITALIA srl
; Author: C.Doglio
; Date: 27.10.04
; File: ICON0937.GSD rev.0.0
;===========================================================
;
#Profibus_DP
;
; Prm-Text-Def-List:
;
;Text definition 1
PrmText=1
Text(0)="LSB first"
Text(1)="MSB first"
EndPrmText
;
;Text definition 2
PrmText=2
Text(0)="Off"
Text(1)="Close"
Text(2)="Open"
Text(3)="Stayput"
Text(4)="Go to position"
EndPrmText
;
;Text definition 3
PrmText=3
Text(0)="Off"
Text(1)="On"
EndPrmText
;
; Ext-User-Prm-Data-Def-List:
;
ExtUserPrmData=1 "Storage Format"
Unsigned8 0 0-1
Prm_Text_Ref=1
EndExtUserPrmData
ExtUserPrmData=2 "Fail safe action"
Unsigned8 0 0-4
Prm_Text_Ref=2
EndExtUserPrmData
ExtUserPrmData=3 "Fail safe delay"
Unsigned8 4 0-255
EndExtUserPrmData
ExtUserPrmData=4 "Safe position"
Unsigned8 50 0-100
EndExtUserPrmData
ExtUserPrmData=5 "Timer Opening"
Unsigned8 0 0-1
Prm_Text_Ref=3
EndExtUserPrmData
ExtUserPrmData=6 "Timer Closing"
Unsigned8 0 0-1
Prm_Text_Ref=3
EndExtUserPrmData
ExtUserPrmData=7 "Timer On time"
Unsigned8 2 2-200
EndExtUserPrmData
ExtUserPrmData=8 "Timer Off time"
Unsigned8 2 1-200
EndExtUserPrmData
ExtUserPrmData=9 "Timer OP-start"
Unsigned8 0 0-100
EndExtUserPrmData
ExtUserPrmData=10 "Timer OP-stop"
Unsigned8 100 0-100
EndExtUserPrmData
ExtUserPrmData=11 "Timer CL-start"
Unsigned8 100 0-100
EndExtUserPrmData
ExtUserPrmData=12 "Timer CL-stop"
Unsigned8 0 0-100
EndExtUserPrmData