2.1 MARKING
IECEx INE XX.ZZZZ = IECEx REFERENCE CERTIFICATE (CoC)
XX ATEX ZZZZ = ATEX REFERENCE CERTIFICATE
0080 = Notified body for ATEX quality assurance (INERIS)
II = Group II (surface industries)
2 = Category 2 apparatus
G = Explosive atmospheres caused by gas, mists or vapors
D = Explosive atmospheres caused by gas dusts
IP66/68 = Degree of protection
Hazardous zone Zone Categories according to 94/9/CE
Directive
Gas, mists or vapours 0 1G
Gas, mists or vapours 1 2G or 1G
Gas, mists or vapours 2 3G or 2G or 1G
Dust 20 1D
Dust 21 2D or 1D
Dust 22 3D or 2D or 1D
Equipment Protection Level (EPL). EN 60079-14
Explosive Atmosphere Zone EPL
Gas 0 Ga
Gas 1 Ga or Gb
Gas 2 Ga or Gb or Gc
Dust 20 Da
Dust 21 Da or Db
Dust 22 Da or Db or Dc