| | | * General monitoring 2 (53) delay
| | | off/0.1..6500.0 [off] s
| | | * Generic monitoring 3 (257)
| | | - off [Default]
| | | - on, stop at floor
| | | - on, immediately
| | | - on, blocked mode at floor
| | | - on, blocked mode immediately
| | | * Text generic monitoring 3 (257)
| | | - Generic monitoring [Default]
| | | - UPS monitoring
| | | - Vandalism monitoring
| | | - Motor protection monitoring
| | | - Safety contactor monitoring
| | | - ...
| | | * Ins/Ero ignores generic monitoring 3 (257)
| | | - off [Default]
| | | - on
| | | * BlueModus ignores generic monitoring 3 (257)
| | | - off [Default]
| | | - on
| | | * General monitoring 3 (257) delay
| | | off/0.1..6500.0 [off] s
| | | * Light supply monitoring (36)
| | | - off
| | | - on [Default]
| | | * Car light monitoring (52)
| | | - off [Default]
| | | - on
| | | * Machine room temp. monitoring (38)
| | | - off
| | | - on [Default]
| | | * Monitoring UPS
| | | - off [Default]
| | | - on
| | | * Supervision control signal door relay
| | | - Off [Default]
| | | - on, with blocking
| | | * Hall door monitoring using separate door contacts
| | | - off [Default]
| | | - on
| | | - on, using supervision signal (720)
| | | * Hall door monitoring 1..127
| | | * Safety barrier monitoring
| | | - off [Default]
| | | - on
| | | * Safety circuit bypass monitoring
| | | - off
| | | - on, stop immediately
| | | - on, stop immediately blocked [Default]
| | | * Separating door monitoring (430)
| | | - off [Default]
| | | - on
| | | * Door sill monitoring (17)
| | | - off [Default]
| | | - on
| | | * Passive safety circuit monitoring
| | | - on, lift blocked [Default]
| | | - on, Without blocking
| | | * Emergency call unit ready signal monitoring
| | | - off [Default]
| | | - on
| | | * Trigger for driving monitoring
| | | - Floor selector impulse [Default]
| | | - Distance covered
| | |
| | +- Emergency power
| | | * Function
| | | - off [Default]
| | | - on using enable signal
| | | - on without enable signal
| | | * Unlock disabled floors
| | | - off
| | | - on [Default]
| | | * Emergency supply journey delay
| | | off/1..255 [off] s
| | | * Cancel remote off
| | | - off [Default]
| | | - on
| | | * Activate drives 2. parameter set
144