Idle lines of the travelling cable should be connected with one end
to the earth at the control cabinet
The components of the control unit conform with the regulations of
DIN EN 81 (TRA) as well as VDE 0100 / 0101 / 0551 / 0660 and
BGV A2. The control cabinets conform to the installation standards
VDE 0660 / part 500.
Mains and auxiliary contactors used in the control unit comply with
DIN EN 81 part 1, 13.2, (TRA 260.82) as well as VDE 0660, but at
least equipment class D3.
Voltage fluctuations are permissible if they range within a tolerance
of +10% to -20% normally guaranteed by the utility company.
Damages for malfunctions caused by an impermissible voltage rise
may not be claimed from the manufacturer.
If owners add further coils (inductivities) at their own discretion, it is
be of utmost importance that these coils are interference-proof as
well.
DC-powered inductivities such as, for example, in contactors,
relays, brake magnets, lock magnets and hydraulic valves must be
equipped with a diode (1000 V / 1 A), anti-parallel and as near as
possible to the coil (BÖHNKE + PARTNER use a free running
diode).
AC-powered contactors, relays, brake magnets, lock magnets and
hydraulic valves are required to be equipped with a RC combina-
tion pitched on the type of coil, in parallel and as near as possible
to the coil (the RC combination of BÖHNKE + PARTNER is univer-
sally usable).
AC-powered door operators, braking and locking motors are to be
equipped with a RC combination pitched to the motor type, in par-
allel and as near as possible to the motor coil. The RC combina-
tions are radially connected to the motor coil (the RC combination
of BÖHNKE + PARTNER is universally usable).
Interference suppression means are to be properly installed.