RPS cannot perform remote
programming and control
Both addresses 0144
and 0145 are set to 0
Program the address
0144 to a number from 1
to 15. Program the
address 0145 to 1
Occasionally abnormal
communication in use of
Contact ID/personal
telephone alarm
Extension system is used
in the telephone network
The telephone network
support ADSL as well
Add dial delay in
programming
Connect the system after
the ADSL filter
No response from the keypad
and the alarm siren
(disabled) when an alarm is
triggered by the zone
The zone silent alarm is
enabled
Disable the zone silent
alarm
The AMAX panel cannot send
any reports (programmed to
send reports to receiver)
The transmission format
of the receiver is
programmed to 0 = not
used
Program the
transmission format of
the receiver to 1 or 3
A-LINK cannot be connected
with ITS- DX4020-G
The parameters of ITS-
DX4020-G are not
properly set.
Recommend to set the
parameter ACK TIMEOUT
of ITS-DX4020-G to the
maximum (600) and set
TRANSMIT BUFFER LIFE
TIME to the maximum
(120)