RPS cannot perform remote
programming and control
– Both addresses 0144
and 0145 are set to 0
– Program the address
0144 to a number from 1
to 15. Program the
address 0145 to 1
Occasionally abnormal
communication in use of
Contact ID/personal
telephone alarm
– Extension system is used
in the telephone network
– The telephone network
support ADSL as well
– Add dial delay in
programming
– Connect the system after
the ADSL filter
No response from the keypad
and the alarm siren
(disabled) when an alarm is
triggered by the zone
– The zone silent alarm is
enabled
– Disable the zone silent
alarm
The AMAX panel cannot send
any reports (programmed to
send reports to receiver)
– The transmission format
of the receiver is
programmed to 0 = not
used
– Program the
transmission format of
the receiver to 1 or 3
A-LINK cannot be connected
with ITS- DX4020-G
– The parameters of ITS-
DX4020-G are not
properly set.
– Recommend to set the
parameter ACK TIMEOUT
of ITS-DX4020-G to the
maximum (600) and set
TRANSMIT BUFFER LIFE
TIME to the maximum
(120)
AMAX 2100 / 3000 / 4000
Troubleshooting | en 139