The detectors (sensors) will be connected between zone and COM terminal through EOL
series connection (open triggered) or EOL parallel connection (short triggered).
The panel sets the short / open as activate when connecting with single EOL.
The valid zone number is 1-8 for AMAX 2100 / 3000, 1-16 for AMAX 4000
Dual EOL: If the tamper supervision is set, we only can use the NC contact point. The EOL
status is:
Loop resistance (ohm)
Zone Status
Min Type Max
o 1430 tamper
1650 2200 2750 normal
2970 4400 4950 triggered
5220 ∞ tamper
Using one 2.2 kilo resistor as EOL of the tamper zone, which works together with the zone
EOL 2.2 kilo.
NC (normally close): If the zone option is set to “NC”, an alarm occurs when the zone is
opened. When the zone is closed, the system is in normal mode.
NO (normally open): If the zone option is set to “NO”, an alarm occurs when the zone is
closed. When the zone is opened, the system is in normal mode.
On-board Tamper Input
A separate input is provided for enclosure tamper. The response time of the tamper input can
be programmed individually. The response time value range is 000.0-999.9 seconds.
Zone Name
This option is used to name zones. Therefore, the numbers on the text keypad function as an
alphabetical input:
Number on the
text keypad
Alphabetical input when number is pressed consecutively
1 . , ' ? ! " 1 - ( ) @ / : _ ¹ ² ³ © ® º « » µ ¶
2 a b c 2 æ å ä à á â ã ç ć č
3 d e f 3 è é ê ë ð ę
AMAX 2100 / 3000 / 4000 Settings | en 59