Modular fire panel Remote Services | en 33
Bosch Sicherheitssysteme GmbH Networking guide 07.2019 | 5.9 | F.01U.247.450
Remote Maintenance for Private Secure Network
Remote Maintenance can be configured for Private Secure Network: Collected data will be
sent to a central management server system (CMS).
!
Caution!
Remote Services require a secure IP connection. Bosch Remote Services or connection with
Private Secure Network is required.
With Private Secure Network an IP network is provided, which is based on DSL with an
optional wireless access on the panel side (EffiLink). Remote Services for Private Secure
Network is only available in Germany with a service agreement with Bosch BT-IE.
Notice!
To connect panels via FX, use media converters approved by Bosch.
Remote
Maintenance via
Private Secure
Network
Service
Center
Figure8.5: Remote Maintenance for Private Secure Network
For Remote Maintenance, you must enter the server IP address and port of the Remote
Maintenance system server in the FSP-5000-RPS programming software.
Assign a unique Panel Network ID to the network.
Switch for connecting the CMS must be programmed separately
Program the IP address and redundancy settings of the switch, see Settings on switch, page
39. As the switch is installed in the immediate vicinity (without intermediate space), the
power supply does not have to be designed redundantly and the fault outputs are therefore
not used.
Make sure that the RSTP settings in the panel controllers, in FSP-5000-RPS and in Ethernet
switch are identical.

Other manuals for Bosch FPA-5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch FPA-5000 and is the answer not in the manual?

Bosch FPA-5000 Specifications

General IconGeneral
Max Number of Detectors per Loop254
DisplayLCD
Network CapabilityYes
Power Supply24 V DC
Operating Temperature-5°C to +50°C
Communication PortsEthernet
Humidity Range95% non-condensing