8 en | System overview Modular fire panel
07.2019 | 5.9 | F.01U.247.450 Networking guide Bosch Sicherheitssysteme GmbH
3 System overview
Ethernet
IP Stack
IP Protocols
Networking over IP
OPC-Server
CAN
Networking
over CAN
Praesideo/PAVIRO
Services
In the network, the Ethernet interface and IP protocols are used for different services. The
Ethernet interface can be disabled completely or its use disabled only for networking over
TCP/IP. Disabling may be necessary for networking over CAN.
Enabling services
– networking over TCP/IP
In FSP-5000-RPS, enable panel-to-panel communication in the Ethernet network
– OPC servers
Add an OPC server to the FSP-5000-RPS configuration
– Praesideo/PAVIRO connection
Add a Voice Alarm System to the FSP-5000-RPS configuration and configure virtual
triggers.
– Remote Services (Remote Connect as prerequisite, Remote Maintenance and Remote
Alert)
Activate the relevant check box in FSP-5000-RPS
– Remote Services (Remote Connect as prerequisite, Remote Maintenance and Remote
Alert) for Private Secure Network
Add remote access to the FSP-5000-RPS configuration and set up the remote access in
FSP-5000-RPS.
Notice!
Unintentionally data transfer
If the Ethernet interface of the panel controller is used only for communicating with an OPC
server or for Remote Services disable the panel communication over TCP/IP, in FSP-5000-
RPS. Otherwise fire data could be transferred over the Ethernet unintentionally.
To operate Ethernet or TCP/IP-based services, the Ethernet interfaces must be enabled and
the correct TCP/IP settings configured.
Network of panels and remote keypads
The table shows the options for networking panels/remote keypads depending on the network
topology and the panel type. Consider the limits determined by the network topology.