38
Start-up
10.2.2 Connecting büS device with Bürkert Communicator
Required components:
• Communications software: Bürkert Communicator for PC
• büS standard set (see accessories)
→ Establish connection to PC with büS stick.
→ Starting Bürkert Communicator.
→ Implementing settings.
10.3 IO-Link
10.3.1 Information, IO-Link
IO-Link is an internationally standardized IO technology (IEC 61131-9) to enable sensors and actuators to
communicate.
IO-Link is a point-to-point communication with 3-wire connection technology for sensors and actuators and
unshielded standard sensor cables.
10.3.2 Technical specications, IO-Link
IO-Linkspecications V1.1.2
Supply via IO-Link (M12 x 1, 4-pin, A-coded)
Port Class A
SIO mode yes, optionally 2xDO (end positions), or1xDI+1xDO (switch
valve + one end position)
IODDle File name: "Buerkert_Werke_GmbH-ControlHead8691-
20170208-IODD1.1.xml"
VendorID 0x78, 120
DeviceID 0x0021F301, 2224897
Transmission speed COM3 (230.4 kbit/s)
M-sequence type in Operate Mode TYPE_2_V
Min. cycle time 1 ms
Data storage Yes
Max. cable length 20 m