65
Start-up
10.4.3.24 0x2C0D CMD set-point
Sub-
index
Name Description
Access type
Factory
reset
0x1 CMD set-point value
source
Select CMD set-point value source:
Congurethesourceofthecontrolsignalforopeningand
closing the valve
0: büS/CanOpen
1: IO-Link
2: Internal button (manual)
3: Manual set-point value (see 0x4)
RW x
0x4 Manual CMD setpoint
Select manual set-point value
0: Close
1: Open
RW
Table 35: 0x2C0D CMD set-point
10.4.3.25 0x2C0E Diagnostics
Sub-
index
Name Description
Access type
Factory
reset
0x1 Totalizer TravelAccu
Travel accumulator total:
Travel distance of the valve spindle from factory default is
added up to determine the service life.
RO
0x2 Totalizer TravelAccu
Service
Travel accumulator resettable:
Travel distance of the valve spindle is added up since last
reset (e.g. once maintenance is complete)
RO
0x3 Totalizer TravelAccu
Service Limit
Travel accumulator: Activate or deactivate maintenance
threshold
0: Diagnostics deactivated
>0: Diagnostics activated
Warning is output when the resettable travel accumu-
lator reaches this threshold
RW x
0x4 Totalizer Valve Cycles
Total number of switching cycles:
Number of all ON/OFF switching cycles performed since
factory default
RO
0x5 Totalizer Valve Cycles
Service
Number of resettable switching cycles:
Number of all ON/OFF switching cycles performed since
last reset.
RO