68
Start-up
10.4.3.26 0x2C0F IO-Link SIO mode settings
Internal object
10.4.3.27 0x2C11 MenuOptionBits
Internal object
10.4.3.28 0x2C13 FactoryReset
Sub-
index
Name Description
Access type
Factory
reset
Factory reset parameters
0: Complete
111: Factory reset start
RW
Table 37: 0x2C13 FactoryReset
10.4.3.29 Baud rates
Theappliedbaudratescanbeconguredin“DeviceCommunicationObject(0x2001sub1)”.Thesupported
baudratesarespeciedintheEDSle.
Possible values:
0: 1000 kbit/s
1: 800 kbit/s (not supported)
2: 500 kbit/s (default)
3: 250 kbit/s
4: 125 kbit/s
5: 100 kbit/s
6: 50 kbit/s
7: 20 kbit/s
8: 10 kbit/s
10.4.3.30 Cyclic data
RPDOs (received data)
1. Receive PDO mapping parameter 0:
Sub1: PDO mapping entry (object 2540sub1)
TPDOs (sent data)
1. Send PDO mapping parameter 0:
Sub1: PDO mapping position (object 2500sub1)
Sub2: PDO mapping end positions (object 2501sub1