53
Start-up
Message Description IO-Link
event code
IO-Link
event type
Action
Temperature error
overload
Device temperature for
operation too high or too
low
0x4000 ERROR Modify ambient temperature.
If fault persists, contact Bürkert
Service
Temperature
warning upper
threshold exceeded
Ambient temperature too
high or excessive friction
in actuator
0x4210 WARNING Reduce ambient temperature.
If fault persists, contact Bürkert
Service.
Temperature
warning lower
threshold exceeded
Ambient temperature too
low
0x4220 WARNING Increase ambient temperature
General power
supply error
Supply voltage for oper-
ation of device too high
or too low
0x5100 ERROR Check supply voltage
Contact Bürkert Service
Voltage warning
upper threshold
exceeded
Supply voltage too high 0x5110 WARNING Check supply voltage
Voltage warning
lower threshold
exceeded
Supply voltage too low 0x5111 WARNING Check supply voltage
Table 20: IO-Link-Events